Variable operating time actuators SQVEx and SQRVEx
With SQVEx .2 part-turn actuators for open-close duty and SQRVEx .2 for modulating duty paired with ACVExC .2 actuator controls, the proven AUMA SQ/SQR range is enhanced by variable operating time models. AUMA is spearheading market technology, offering a wide operating time range with a ratio of up to 1:10.
Actuators of the SQVEx type range are rated for open-close duty and positioning duty (classes A and B) / (short-time duty S2 - 15 min).
Actuators of the SQRVEx type range are rated for modulating duty (class C) S4 - 25 %.
-
Details
-
Design features SQVEx
- Torque range from 150 Nm to 2,400 Nm
- Swing angle from 75° to 105°
- Operating times for 90° from 4 s to 360 s
- Limit and torque sensing
- Mains connection: 1-phase and 3-phase
- Handwheel for manual operation
- Mechanical position indicator
-
Design features SQRVEx
- Torque range from 150 Nm to 2,400 Nm
- Modulating torque range from 75 Nm to 1,200 Nm
- Max. number of starts 1,500 c/h
- Swing angle from 75° to 105°
- Operating times for 90° from 4 s to 360 s
- Limit and torque sensing
- Mains connection: 1-phase and 3-phase
- Handwheel for manual operation
- Mechanical position indicator
-
Ambient conditions
- High enclosure protection
- High quality corrosion protection
- Wide ambient temperature ranges
-
Options
- Intermediate position switches
- Switches in tandem version
- Remote position transmitter
- Magnetic limit and torque transmitter
-
Interfaces
- Electrical connection via AUMA plug/socket connector
(terminals as an option) - Cable entries in different versions
- Output drive types according to DIN and EN ISO standards
- Electrical connection via AUMA plug/socket connector
-
Interface and functional properties
- Programmable, potential-free output contacts for status signalling
- Soft start and stop for gentle valve operation
- Avoiding pressure surge by an operating time profile
- EMERGENCY behaviour and safety behaviour with separate operating time setpoints
- Process controller (PID)
- Fieldbus control
- Behaviour in case of emergency situations and communication loss (programmable)
- Operation data logging
- Bluetooth interface to notebook and Android tablet.
-
Approvals
-
Europe - ATEX
Standard:
II 2G Ex db eb IIC T4 oder T3 Gb
II 2G Ex h IIC T4 oder T3 GbOptional:
II 2G Ex db IIC T4 oder T3 Gb
II 2G Ex db eb IIB T3 Gb
II 2G Ex db IIB T3 Gb
II 2G Ex h IIB T3 Gb - International level/Australia - IEC
Standard:
Ex db eb IIC T4 oder T3 GbOptional:
Ex db IIC T4 oder T3 Gb
Ex db eb IIB T3 Gb
Ex db IIB T3 Gb
-
-
-
Documents
20 documents are found!Dimensions
Electrical data
Operation instructions
Short instructions
Spare parts list
Technical data